Page Numbers: Yes   X: 527   Y: 10.5"   First Page: 98Columns: 1   Edge Margin: .4"   Between Columns: .4"Margins:   Top: 1.3"   Bottom: .75"Line Numbers: No   Modulus: 5   Page-relativeEven Heading:qk40(635)	Appendix					   Maxc Operationsy756qk40(0,4233)(1,13053)\f5b1f0i8f5I23f1BOdd Heading: qk40(635)Maxc Operations	Appendixy756qk40(0,15875)(1,65535)\f5b16f0i8f1BIMAXC Room Power Down/Up Procedurey648x6(635)\f9bby Ron Weaverz18697e24(0,5152)\f6bOCTOBER 1980(Revised January 1, 1982)Filed on [Indigo]<Maxc>MaxcOpsPowerDownUp.Bravoz18697e24\f7b13Bi25I48bAbstract: This procedure itemizes the chronological steps necessary to systematically shut down the power in the Maxc room when a known power outage is scheduled.	z18697x6e54j\f6b10B152f0 1f6EMERGENCY shutdown procedure (for fire or smoke) may be found in Appendix A.	z18697x6e12j(635)\f6b10B66f0 1f6A version of this procedure will appear in the Maxc Operations manual.	z18697x6e12j\f6 47i16I7f0 1f6XEROXz18697l10230y144\f2 5f7bPALO ALTO RESEARCH CENTER3333 Coyote Hill Road / Palo Alto / California 94304l10239(2116)\f6b26f71. Prior to Shutdowny720x6e36k792(635)\f5bIn order to give users adequate notice and to protect files on disk, Tenex should ordinarily be stopped in the following manner.	d3705x6e10jk40	Forty-eight hours prior to the scheduled power outage send a message to the NCC Coordinator and the Arpanet liaison at SCI via their Arpanet mailboxes CONTROL@BBNC and Green@SCI-ICS stating the period the power will be off and that the IMP will be affected.  If the scheduled power outage is to take place in less than 48 hours then the NCC Coordinator may be reached direct by phone: (617) 661-0100.  The controller may wish you to call him just prior to taking the system down so you can set some switches on the IMP panel.		As long as possible before the scheduled downtime (preferably 24 hours or more), notify users by (optionally) putting a notice in the login message, setting the system downtime cell and recording a telephone message.  	x6e10jk40A.	To put a notice in the login message, login as yourself and:	x6e10jk40@SNDMSG<cr>To: SYSTEM<cr>cc:<cr>Subject: Scheduled downtime<cr>	Message:(An appropriate message giving date, time, and reason)	^ZQ,S,?,carriage-return:<cr>SYSTEM -- ok	@l5468x6e10jk40\1u10U5u10U4u4U10u22U67u2U23u4UB.	To set the system downtime cell, you must be a wheel or a maintenance person:	x6e10jk40@ENABLE<cr>		(only if you are a wheel)	!HALT,<cr>		(do not omit the comma)	[Superpassword:]GUESS<cr>!!AT mm/dd/yy/ hh:mm<cr>					(date & time system going down)!!UNTIL mm/dd/yy hh:mm<cr>					(date & time coming back up)!!DUE (TO REASON) reason (type ? for list)<cr>	!!<cr>!l5468x6e10jk40\1u10U3i4I14i5I4u9U6i3I34u9U3u22U39u24U36u22U18u4U4u4UC.	To record a telephone message, go to the recording telephone (next to the Imp in the back room) and follow the instructions posted there.	x6e10jk402.  System Shutdown	x6e12jk40\f5b19f0B	General Methodology:			(1) Shut down software systems cleanly			(2) Safeguard rotary storage by spinning down all disk drives			(3) Get all other power off in the simplest manner possible so that restart can be accomplished		    without an excessive current surge.	x6e12jk40\1i20I1i41I1i64I1i140I	Maxc	x6e12jk40\b5BThe system will automatically start notifying users of the impending downtime beginning one hour before it is to occur.  When the zero hour arrives, all jobs will be forcibly logged out except any job logged in on the Maxc controlling terminal, new logins will be prevented, and "Shutdown Complete" will type out on the Maxc console.  If there are now no jobs logged in, Tenex will shortly hit a BUGCHK (EDDT breakpoint) at SWHLT1, at which point Tenex is properly halted.	l5468x6e6jk40If there is a job logged in on the Maxc controlling terminal, it will be necesary to halt Tenex manually.  To do this (for which you must be a wheel):	l5468x6e6jk40\143i5I@ENABLE<cr>!QUIT<cr>.Halt Tenex.	l6703x6e12jk40\1u10U2u8U2u1U9u1UWait for the EDDT preakpoint at SWHLT1.  A message such as "$8B>>CHKADR BUGCHK/ SWHLT1" should be printed out.	l5468x6e6jk40Once the Maxc2 system have halted you may proceed by stopping the rest of the systems in the Maxc room.	l5468x6e6jk40	Alpinex6e12jk40\b7B	Ivy		 From an Alto or DLS terminal:	x6e12jk40\1b3BChat Ivy<cr>	Ena<cr>			NOTE 1:	You must be an Ivy wheel.	Halt<cr>Quit<cr>l5468x6e6jk40\24bi7BI20i5I	Twinklex6e12jk40\1b7BCtrl-Shift-D		(to turn on display)	Position cursor over "gateway" window, press down middle button, select "gateway" menu, let up button.Press down middle button, select "quit" item, let up button.	l5468x6e6jk40	DLSx6e12jk40\1b3BQuit<cr>l5468x6e6jk403.  Removing System Power	x6e12jk40\f5b25f0B	Maxc Disk Drives	x6e12jk40\1b16BTurn off Front switch first, then the switch in the rear.	l5468x6e12jk40NOTE 2:	An alternate procedure, (which is not advised due to the fact that some				circuit breakers may be in the off state prior to shutdown for some reason,				and the difficulty in correctly identifying all of them may lead to errors				when restoring power) instead of turning off the switch in the rear of each				disk drive, is to wait until everything else in this section has been done and				then throw all the circuit breakers on the Maxc, Maxc-A and Maxc-B Circuit				Breaker Panels, noting carefully the ones which are already off.	l6703x3e12jk40\bi8f1BI34ui3UI456i16I1i30I1f0	Maxcx6e12jk40\1b4BPress middle blank button then type	3301PM.With the left mouse button successively select the menu items "Power Off" and	"Both".l5468x6e12jk40			NOTE 4:	(The message "Processor locked on" will appear.  Just shut off the							processor power supply manually.  The automatic power-off									circuitry is missing.)	l5468x6e12jk40\3bi7BI1f1 131f0 8f1 23f0Spin down ALTO disk	Throw CKT breaker on front of Processor	Throw CKT breakers on all power supplies (front).	Pull 20 amp CKT breaker on panel above ALTO.	l5468x6e12jk40	Twinkle	x6e12jk40\1b7BSpin down disks (wait until they stop)	Pull out upper blower drawer and turn off switch inside top left.	l5468x6e12jk40\16i22I	Alpinex6e12jk40\1b6Bl5468x6e12jk40	Ivyx6e12jk40\1b3BSpin down disks (ALTO & six Trident disks)	Turn off ALTO power switch	Turn off T80 & T300 disk power switches (in rear, or see NOTE 2 on page 3)	l5468x6e12jk40\129bi6BI	DLSx6e12jk40\1b3BSpin down disk and (after it stops) pull 15 amp CKT breaker above.	l5468x6e12jk40\19i17I	IMPx6e12jk40\1b3BDon't worry about it unless NCC has asked you from an earlier phone call to call		just before removing power.	NCC likes to be called two days before scheduled shutdowns.	l5468x6e12jk40	Doradosx6e12jk40\1b7BFor each Dorado, if it is not already powered off (green light 5 flash) find its	 			terminal and press boot button seven times in quick succession to shut down.	Wait until green lights are flashing fives before throwing CKT breakers.	l5468x6e12jk40\50i21I4.	Start Up Sequence:x6e12jk40\f5b21B	Close only those circuit breakers on panels marked Maxc, Maxc-A, & Maxc-B, that were opened	during the initial powerdown sequence.	x6e12jk40\7ui4UI	Twinkle	(Should be started first for Date & Time source to other systems.)	x6e12jk40\1b7B1bi66BITurn on AC Power and spin up disks	Boot ALTO	Type GATEWAY<cr>	(2 minutes to come on)	l5468x6e12jk40	NOTE 5:	Don't bring anything else up until message "Gateway in operation" appears on		Twinkle screen, or 1 minute after screen turns blank, whichever occurs first.	l5468x6e12jk40(0,6350)(1,8128)\1bi4B1b2BI1f1 156f0 Remaining machines can be started in any order (or simultaneously).	x6e12jk40(635)\1bi67BI	DLSx6e12jk40\1b3BSet CKT breaker	Spin up disk	Boot ALTO	Type DLSCONTROL	l5468x6e12jk40	Maxcx6e12jk40\1b4BTurn on ALTO	Spin up ALTO disk	Turn on all Processor and Memory cabinet power supplies	Boot the Alto and run the Midas subsystem.  With the left mouse button,	succesively select the menu items "Power On", "Both", and "Do-It".	Turn on Disk drive AC power (in rear) then front panel switches	l5468x6e12jk40	WARNING:	Wait at least 10 seconds between spinning				up each drive to allow for the starting surge.	l5468x6e12jk40(0,6350)\bi9BINormally the configuration is set up properly; just type MIDAS TENGO.	See Section 5 & 6 of Maxc Operations for abnormal situations.	l5468x6e12jk40(635)\92bi15BIAfter all disk drives are ready you may start AltIO and start Tenex by	selecting "Run-Prog", "Tengo" with the mouse.	l5468x6e12jk40(0,6350)	Alpinex6e12jk40(635)\1b6Bl5468x6e12j	Ivy x6e12jk40\1b3BTurn on ALTO	Spin up Diablo disk	Turn on Trident disks AC power	Spin up Trident Disks	BootType IFS	l5468x6e12j	Doradosx6e12jk40\1b7BTurn on Breakers (that's all)	l5468x6e12jk40	Impx6e12jk40\1bShould restart by itself.  Call NCC to verify correct operation.	l5468x6e12jk40Referencesx6e36k120\b1.	Edward R. Fiala, Charles M. Geschke, Edward Taft, and Ronald L. Weaver Maxc Operations, XEROX, August 26, l983.	l3696d2992x3e6jk40(0,3712)(1,65535)\74bi15BI(635)